-64-
11. OTHER PROGRAMMING
11.5 Alarm
3 Programming Mode
1) Absolute value alarms (
,
,
,
)
(Note) Program the alarm value within the scale range.
2) Rage-of-change alarm (
,
)
(Note 1) Program the alarm value with the change width (without sign) per unit time.
(Note 2) Unit time = measuring interval (about 0.1 sec.) x measuring count
Program this measuring count (1 to 20).
3) Differential alarm (
,
,
,
)
(Note 1) Program an alarm value with a difference (without sign) between measured values of channels.
(Note 2) Program another channel to be compared.
* In the standard specifications, the relay No. is fixed to “0” and the cursor does not appear. Program the relay
No. for the alarm output (option) only. See Section 12.2.
Level
larm
type
Relay No.*
Alarm value (Note)
Max. 5 digits by left-justify
Unused digits are filled with spaces.
Characte
displa
Curso
Measuring count (Note 2) (1 to 20)
Channel to be compared (Note 2)
Characte
displa
Curso
Curso
Characte
displa
Channel
Channel
Level
Level
larm
type
larm
type
Relay No.*
Relay No.*
Alarm value (Note 1)
Max. 5 digits by left-justify
Unused digits are filled with spaces.
Alarm value (Note 1)
Max. 5 digits by left-justify
Unused digits are filled with spaces.